| General information |
| Product type designation | SB 1222, DQ 4x24 V DC 200 kHz |
| Input current |
| from backplane bus 5 V DC, typ. | 35 mA |
| Power loss |
| Power loss, typ. | 0.5 W |
| Digital outputs |
| Number of digital outputs | 4; MOSFET, solid-state (current-sinking/current-sourcing) |
| ● in groups of | 4 |
| Short-circuit protection | No |
| Switching capacity of the outputs |
| ● with resistive load, max. | 0.1 A |
| Load resistance range |
| ● upper limit | 11 Ω |
| Output voltage |
| ● Rated value (DC) | 24 V |
| ● for signal "0", max. | 1 V; with 10 kOhm load |
| ● for signal "1", min. | L+ (-1.5 V) |
| Output current |
| ● for signal "1" rated value | 0.1 A |
| ● for signal "1" permissible range, max. | 0.1 A |
| Cable length |
| ● shielded, max. | 50 m |
| Interrupts/diagnostics/status information |
| Diagnostics indication LED |
| ● for status of the outputs | Yes |
| Standards, approvals, certificates |
| CE mark | Yes |
| CSA approval | Yes |
| UL approval | Yes |
| cULus | Yes |
| FM approval | Yes |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| Marine approval | Yes |
| Ambient conditions |
| Free fall |
| ● Fall height, max. | 0.3 m; five times, in product package |
| Ambient temperature during operation |
| ● min. | -20 °C |
| ● max. | 60 °C |
| ● horizontal installation, min. | -20 °C |
| ● horizontal installation, max. | 60 °C |
| ● vertical installation, min. | -20 °C |
| ● vertical installation, max. | 50 °C |
| Ambient temperature during storage/transportation |
| ● min. | -40 °C |
| ● max. | 70 °C |
| Air pressure acc. to IEC 60068-2-13 |
| ● Storage/transport, min. | 660 hPa |
| ● Storage/transport, max. | 1 080 hPa |
| Relative humidity |
| ● Operation at 25 ℃ without condensation, max. | 95 % |
| Mechanics/material |
| Enclosure material (front) |
|
| ● Plastic | Yes |
| Dimensions |
| Width | 38 mm |
| Height | 62 mm |
| Depth | 21 mm |
| Weights |
| Weight, approx. | 35 g |