| input |
| type of the power supply network | 1-phase AC |
| supply voltage at AC |
|
| ● minimum rated value | 100 V |
| ● maximum rated value | 240 V |
| ● initial value | 85 V |
| ● full-scale value | 264 V |
| input voltage at DC | 88 ... 370 V |
| wide range input | Yes |
| buffering time for rated value of the output current in the event of power failure minimum | 20 ms |
| operating condition of the mains buffering | at Vin = 170 V |
| line frequency | 50/60 Hz |
| line frequency | 47 ... 63 Hz |
| input current |
|
| ● at rated input voltage 120 V | 1.65 A |
| ● at rated input voltage 230 V | 0.75 A |
| current limitation of inrush current at 25 °C maximum | 30 A |
| I2t value maximum | 1.5 A²·s |
| fuse protection type | internal |
| fuse protection type in the feeder | Recommended miniature circuit breaker: 10 A characteristic C |
| output |
| voltage curve at output | Controlled, isolated DC voltage |
| output voltage at DC rated value | 24 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 22.8 ... 26.4 V |
| relative control precision of the output voltage |
|
| ● on slow fluctuation of input voltage | 0.1 % |
| ● on slow fluctuation of ohm loading | 0.5 % |
| voltage peak |
|
| ● maximum | 50 mV |
| ● typical | 25 mV |
| display version for normal operation | Green LED for 24 V OK |
| behavior of the output voltage when switching on | Overshoot of Vout < 1 % |
| response delay maximum | 0.5 s |
| voltage increase time of the output voltage |
|
| ● typical | 50 ms |
| output current |
|
| ● rated value | 3 A |
| ● rated range | 0 ... 3 A; +55 ... +70 °C: Derating 3.5%/K |
| supplied active power typical | 72 W |
| bridging of equipment | Yes |
| number of parallel-switched equipment resources for increasing the power | 2 |
| efficiency |
| efficiency in percent | 89 % |
| power loss [W] |
|
| ● at rated output voltage for rated value of the output current typical | 9 W |
| closed-loop control |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.2 % |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3 % |
| setting time |
|
| ● load step 10 to 90% typical | 1 ms |
| ● load step 90 to 10% typical | 1 ms |
| protection and monitoring |
| design of the overvoltage protection | < 28.8 V |
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Constant current characteristic |
| response value current limitation | 3.6 ... 4.4 A |
| ● typical | 4 A |
| enduring short circuit current RMS value |
|
| ● typical | 4 A |
| safety |
| galvanic isolation between input and output | Yes |
| galvanic isolation | Safety extra low output voltage Vout according to EN 60950-1 |
| operating resource protection class | Class I |
| leakage current |
|
| ● maximum | 3.5 mA |
| protection class IP | IP20 |
| EMC |
| standard |
|
| ● for emitted interference | EN 55022 Class B |
| ● for mains harmonics limitation | EN 61000-3-2 |
| ● for interference immunity | EN 61000-6-2 |
| standards, specifications, approvals |
| certificate of suitability |
|
| ● CE marking | Yes |
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
| ● UKCA marking | No |
| ● EAC approval | No |
| ● Regulatory Compliance Mark (RCM) | No |
| ● CCC approval | Yes |
| ● NEC Class 2 | No |
| type of certification |
|
| ● BIS | Yes; R-41184349 |
| ● CB-certificate | Yes |
| MTBF at 40 °C | 500 000 h |
| MTBF at 25 °C | according to MIL-HDBK-217F, 100% full load (24 V, 3 A), input voltage: 220 V AC |
| standards, specifications, approvals hazardous environments |
| certificate of suitability |
|
| ● IECEx | No |
| ● ATEX | No |
| ● ULhazloc approval | No |
| ● cCSAus, Class 1, Division 2 | No |
| ● FM registration | No |
| standards, specifications, approvals marine classification |
| shipbuilding approval | No |
| Marine classification association |
|
| ● American Bureau of Shipping Europe Ltd. (ABS) | No |
| ● French marine classification society (BV) | No |
| ● Det Norske Veritas (DNV) | No |
| ● Lloyds Register of Shipping (LRS) | No |
| ambient conditions |
| ambient temperature |
|
| ● during operation | -25 ... +70; With natural convection |
| ● during transport | -40 ... +85 |
| ● during storage | -40 ... +85 |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| connection method |
| type of electrical connection | screw terminal |
| ● at input | L, N, PE: screw terminal for 0.5 ... 6 mm² single-core / 0.5 ... 4 mm² finely stranded |
| ● at output | +1, +2, -1, -2: screw terminal for 0.5 ... 4 mm² |
| mechanical data |
| width × height × depth of the enclosure | 45 × 10 × 81 mm |
| installation width × mounting height | 85 mm × 140 mm |
| required spacing |
|
| ● top | 20 mm |
| ● bottom | 20 mm |
| ● left | 20 mm |
| ● right | 20 mm |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| ● standard rail mounting | Yes |
| ● S7 rail mounting | No |
| ● wall mounting | Yes |
| housing can be lined up | No |
| net weight | 0.46 kg |
| additional information |
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |