| Supply voltage |
| Rated value (DC) | 24 V; 1L+ |
| Reverse polarity protection | Yes |
| Load voltage L+ |
| ● Rated value (DC) | 24 V; 2L+, 3L+ |
| ● Reverse polarity protection | No |
| Input current |
| from supply voltage 1L+, max. | 75 mA |
| from load voltage 2L+ (without load), max. | 100 mA |
| from load voltage 3L+ (without load), max. | 100 mA |
| from backplane bus 5 V DC, max. | 100 mA |
| Power loss |
| Power loss, typ. | 12 W |
| Digital outputs |
| Number of digital outputs | 8 |
| Short-circuit protection | Yes |
| Limitation of inductive shutdown voltage to | L+ (-33 V) |
| Switching capacity of the outputs |
| ● on lamp load, max. | 5 W |
| Output voltage |
| ● for signal "1", min. | L+ (-1.0 V) |
| Output current |
| ● for signal "1" rated value | 2 A |
| ● for signal "1" permissible range for 0 to 40 °C, min. | 7 mA |
| ● for signal "1" permissible range for 0 to 40 °C, max. | 2 A; 2 A for horizontal installation, 1 A for vertical installation |
| ● for signal "1" permissible range for 40 to 60 °C, min. | 7 mA |
| ● for signal "1" permissible range for 40 to 60 °C, max. | 1 A; for horizontal installation |
| ● for signal "0" residual current, max. | 0.5 mA |
| Switching frequency |
| ● with resistive load, max. | 30 Hz |
| ● with inductive load, max. | 2 Hz |
| ● on lamp load, max. | 10 Hz |
| Total current of the outputs (per group) |
| horizontal installation |
| — up to 40 °C, max. | 7.5 A |
| — up to 60 °C, max. | 5 A |
| vertical installation |
| — up to 40 °C, max. | 5 A |
| Cable length |
| ● shielded, max. | 200 m; 200 m for SIL 3, AK 6, Cat 4 |
| ● unshielded, max. | 200 m |
| Interrupts/diagnostics/status information |
| Alarms |
| ● Diagnostic alarm | Yes; Parameterizable |
| Diagnoses |
| ● Diagnostic information readable | Yes |
| Diagnostics indication LED |
| ● Fail-safe operation | Yes |
| ● Group error SF (red) | Yes |
| Potential separation |
| Potential separation digital outputs |
| ● between the channels | Yes |
| ● between the channels, in groups of | 4 |
| ● between the channels and backplane bus | Yes |
| ● between the channels and the power supply of the electronics | Yes |
| Isolation |
| Isolation tested with | 500 V DC/350 V AC |
| Standards, approvals, certificates |
| Highest safety class achievable in safety mode |
| ● acc. to EN 954 | Cat. 4 |
| ● Performance level according to ISO 13849-1 | e |
| ● SIL acc. to IEC 61508 | SIL 3 |
| connection method |
| required front connector | 40-pin |
| Dimensions |
| Width | 80 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights |
| Weight, approx. | 465 g |