| Supply voltage |
| Load voltage L+ |
| ● Rated value (DC) | 24 V |
| Input current |
| from supply and load voltage L+ (without load), max. | 110 mA |
| from backplane bus 5 V DC, max. | 55 mA |
| Power loss |
| Power loss, typ. | 3 W |
| Analog inputs |
| Number of analog inputs | 4 |
| ● For voltage measurement | 4 |
| permissible input voltage for voltage input (destruction limit), max. | 20 V |
| permissible input current for current input (destruction limit), max. | 40 mA |
| Cycle time (all channels) max. | 5 ms |
| Input ranges |
| ● Voltage | Yes |
| ● Current | Yes |
| ● Thermocouple | No |
| ● Resistance thermometer | No |
| ● Resistance | No |
| Input ranges (rated values), voltages |
| ● 0 to +10 V | Yes |
| — Input resistance (0 to 10 V) | 100 kΩ |
| Input ranges (rated values), currents |
| ● 0 to 20 mA | Yes |
| — Input resistance (0 to 20 mA) | 50 Ω |
| Cable length |
| ● shielded, max. | 200 m |
| Analog outputs |
| Number of analog outputs | 2 |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 11 mA |
| Current output, no-load voltage, max. | 15 V |
| Output ranges, voltage |
| ● 0 to 10 V | Yes |
| Output ranges, current |
| ● 0 to 20 mA | Yes |
| Load impedance (in rated range of output) |
| ● with voltage outputs, min. | 5 kΩ |
| ● with voltage outputs, capacitive load, max. | 1 µF |
| ● with current outputs, max. | 300 Ω |
| ● with current outputs, inductive load, max. | 1 mH |
| Cable length |
| ● shielded, max. | 200 m |
| Analog value generation for the inputs |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. | 8 bit |
| ● Integration time, parameterizable | No |
| Analog value generation for the outputs |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. | 8 bit |
| ● Conversion time (per channel) | 500 µs |
| Settling time |
| ● for resistive load | 0.3 ms |
| ● for capacitive load | 3 ms |
| ● for inductive load | 0.3 ms |
| Encoder |
| Connection of signal encoders |
| ● for voltage measurement | Yes |
| ● for current measurement as 2-wire transducer | No |
| ● for current measurement as 4-wire transducer | Yes |
| Errors/accuracies |
| Operational error limit in overall temperature range |
| ● Voltage, relative to input range, (+/-) | 0.9 % |
| ● Current, relative to input range, (+/-) | 0.8 % |
| ● Voltage, relative to output range, (+/-) | 0.6 % |
| ● Current, relative to output range, (+/-) | 1 % |
| Basic error limit (operational limit at 25 °C) |
| ● Voltage, relative to input range, (+/-) | 0.7 % |
| ● Current, relative to input range, (+/-) | 0.6 % |
| ● Voltage, relative to output range, (+/-) | 0.5 % |
| ● Current, relative to output range, (+/-) | 0.5 % |
| Interrupts/diagnostics/status information |
| Alarms | No |
| Diagnostics function | No |
| Potential separation |
| Potential separation analog inputs |
| ● between the channels and backplane bus | No |
| Potential separation analog outputs |
| ● between the channels | No |
| ● between the channels and backplane bus | No |
| ● between the channels and the power supply of the electronics | Yes |
| Isolation |
| Isolation tested with | 500 V DC |
| connection method |
| required front connector | 20-pin |
| Dimensions |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weights |
| Weight, approx. | 285 g |