| Supply voltage |
| Rated value (DC) | 24 V |
| Reverse polarity protection | Yes |
| Load voltage L+ |
| ● Rated value (DC) | 24 V |
| ● Reverse polarity protection | Yes |
| Input current |
| From power supply L+, typ. | 150 mA |
| from backplane bus 5 V DC, max. | 90 mA |
| Power loss |
| Power loss, typ. | 4.5 W |
| Analog inputs |
| Number of analog inputs | 6 |
| permissible input current for current input (destruction limit), max. | 40 mA |
| Input ranges |
| ● Voltage | No |
| ● Current | Yes |
| ● Thermocouple | No |
| ● Resistance thermometer | No |
| ● Resistance | No |
| Input ranges (rated values), currents |
| ● 0 to 20 mA | Yes |
| — Input resistance (0 to 20 mA) | 150 Ω; typ. 150 ohms max. 175 ohms |
| ● 4 mA to 20 mA | Yes |
| — Input resistance (4 mA to 20 mA) | 150 Ω; typ. 150 ohms max. 175 ohms |
| Cable length |
| ● shielded, max. | 1 000 m |
| Analog value generation for the inputs |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. | 16 bit; 15 bit + sign |
| ● Integration time (ms) | 20 ms @ 50 Hz, 16.7 ms @ 60 Hz |
| ● Interference voltage suppression for interference frequency f1 in Hz | f=n x (f1 ±0.5 %) |
| Encoder |
| Connection of signal encoders |
| ● for current measurement as 2-wire transducer | Yes |
| ● for current measurement as 4-wire transducer | Yes |
| Errors/accuracies |
| Operational error limit in overall temperature range |
| ● Current, relative to input range, (+/-) | 0.2 %; 40 µA |
| Basic error limit (operational limit at 25 °C) |
| ● Current, relative to input range, (+/-) | 0.1 % |
| Interrupts/diagnostics/status information |
| Diagnostics function | Yes |
| Alarms |
| ● Diagnostic alarm | Yes |
| Diagnoses |
| ● Diagnostic information readable | Yes |
| Diagnostics indication LED |
| ● Fail-safe operation | Yes |
| ● Group error SF (red) | Yes |
| ● Encoder supply Vs (green) | No |
| Potential separation |
| Potential separation analog inputs |
| ● between the channels | Yes |
| ● between the channels and backplane bus | Yes |
| ● between the channels and the power supply of the electronics | Yes |
| Isolation |
| Isolation tested with | 370V for 1 min |
| Standards, approvals, certificates |
| Highest safety class achievable in safety mode |
| ● acc. to EN 954 | 4 |
| ● Performance level according to ISO 13849-1 | e |
| ● SIL acc. to IEC 61508 | SIL 3 |
| connection method |
| required front connector | 20-pin |
| Dimensions |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights |
| Weight, approx. | 350 g |